Simple user interface

2 Position mode select (Auto/Manual)

Compatible with all conventional detectors

Compact low profile enclosure

Through ‘Metron’ actuator or solenoid monitoring

Zonal volt free contacts

 

 
Home | Corporate | Products | Sales Support | Technical Support | Privacy Policy | Contact Us

GFM-ECP Fire Extinguishing Control Panel
2/4 ZONE (CONVENTIONAL)

 

 

 

Complies with EMC directive

Complies with low voltage directive

2 Selectable discharge duration

Selectable time delay

Ability to operate Silence & reset remotely

Volt free first and second stage contacts

 

SPECIFICATIONS
Model
GFS-ECP 2/4 ZONES
1st stage Sounder outputs
Relay outputs
2nd stage Sounder outputs
Relay outputs
Alarm contact
Volt free changeover 1A at 30VDC
Remote signal contact
Volt free changeover 1A at 30VDC
Remote control inputs
Silence and Reset via volt free
Time delay
5~60 second
Operating Voltage
220VAC
Power supply rating
5A
Battery
7Ah 12V, two per panel
Extinguishant circuit output
Fused at 1A
Auxiliary DC output
Fused at 500mA (250mA max.)
Detection line voltage
24VDC (40mA max.)
Detection line quiescent current
1.6mA max. per zone
Standby current
160mA
Alarm current
320mA
Operating Temperature
32°F to 113°F (0°C to 45°C)
Operating Humidity
Up to 95%, non-condensing
Construction
1.2mm fully welded sheet steel
Finish
Epoxy powder coat
Standard color
2 Tone grey or cream & brown
Dimensions
425mm x 355mm x 152mm
Weight
8Kg approx

 

Home | Corporate | Products | Sales Support | Technical Support | Privacy Policy | Contact Us
Copyright © 2013 Guardall - System of Canada. All rights reserved.